Fire and electrical safety requirements for UPS power supply equipment

The UPS battery room should be equipped with a gas fire extinguishing system or a fine water mist fire extinguishing system. When using a pipeline gas fire extinguishing system, the battery room should be equipped with two independent fire detectors at the same time, and the fire alarm system should be linked with the fire extinguishing system; When using the total flooding method for fire extinguishing, the fire extinguishing system controller should be linked to control the closure of air doors and dampers in the room, stop air conditioning units and exhaust fans, and cut off non fire power sources before the fire extinguishing equipment is activated. When using lithium batteries, an automatic sprinkler fire extinguishing system should be installed in the battery room.
Fire extinguishing facilities
  
The UPS battery room should be equipped with a gas fire extinguishing system or a fine water mist fire extinguishing system. When using a pipeline gas fire extinguishing system, the battery room should be equipped with two independent fire detectors at the same time, and the fire alarm system should be linked with the fire extinguishing system; When using the total flooding method for fire extinguishing, the fire extinguishing system controller should be linked to control the closure of air doors and dampers in the room, stop air conditioning units and exhaust fans, and cut off non fire power sources before the fire extinguishing equipment is activated. When using lithium batteries, an automatic sprinkler fire extinguishing system should be installed in the battery room. In the medical structure, with the development of information technology and the leap of intelligence, the application of uninterruptible power supply (UPS) system has become increasingly widespread and popular. In order to ensure patient safety, medical institutions need to ensure uninterrupted power supply in their buildings. Therefore, UPS uninterruptible power supply has become indispensable. Compared to commercial or industrial use, medical institutions require higher standards for UPS uninterruptible power supply protection systems. Most of the electrical loads in hospitals are primary and secondary loads, which require high continuity and reliability of power supply. Air conditioning system equipment is the main power consuming equipment in hospitals and requires focused management of electricity usage; Class II medical facilities have high requirements for power supply continuity and reliability, and require comprehensive monitoring; Important medical technology laboratory equipment is sensitive to power quality and requires special attention.

2、 Alarm device
The UPS equipment room should be equipped with automatic fire alarm devices, and the alarm signals should be directly connected to the fire control room, in accordance with the relevant provisions of the “Design Code for Automatic Fire Alarm Systems” GB50116. The primary factors for selecting UPS uninterruptible power supplies for medical equipment are high stability and reliability. Most medical equipment belongs to precision instruments, with high requirements for electrical continuity. The quality of electrical energy determines whether medical equipment can operate normally, especially for large and specific high-precision, cutting-edge medical equipment, which has strict requirements for electrical energy quality.
The area where the gas fire extinguishing system is installed should be equipped with fire alarm devices. Fire extinguishing display lights should be installed above the doors outside the area. The control box (cabinet) of the fire extinguishing system should be located outside the room for easy operation, and protective devices should be installed to prevent accidental operation. The demand in the medical industry is far beyond data centers. The mobile information technology solution for the medical industry also requires a secure and stable UPS uninterruptible power supply guarantee. For precision instruments such as CT machines, MRI machines, surgical auxiliary machines, etc., power frequency online UPS power supply can be used for protection. UPS is an online dual conversion UPS with zero conversion time and an online mode efficiency of up to 96%. Multiple communication interfaces can be linked and controlled with medical equipment. Three sets of output sockets are independently controlled to manage the opening and closing of multiple medical devices according to different timing sequences.