Fire and electrical safety requirements for UPS power supply equipment

The UPS battery room should be equipped with a gas fire extinguishing system or a fine water mist fire extinguishing system. When using a pipeline gas fire extinguishing system, the battery room should be equipped with two independent fire detectors at the same time, and the fire alarm system should be linked with the fire extinguishing system; When using the total flooding method for fire extinguishing, the fire extinguishing system controller should be linked to control the closure of air doors and dampers in the room, stop air conditioning units and exhaust fans, and cut off non fire power sources before the fire extinguishing equipment is activated. When using lithium batteries, an automatic sprinkler fire extinguishing system should be installed in the battery room.
Fire extinguishing facilities
The UPS battery room should be equipped with a gas fire extinguishing system or a fine water mist fire extinguishing system. When using a pipeline gas fire extinguishing system, the battery room should be equipped with two independent fire detectors at the same time, and the fire alarm system should be linked with the fire extinguishing system; When using the total flooding method for fire extinguishing, the fire extinguishing system controller should be linked to control the closure of air doors and dampers in the room, stop air conditioning units and exhaust fans, and cut off non fire power sources before the fire extinguishing equipment is activated. When using lithium batteries, an automatic sprinkler fire extinguishing system should be installed in the battery room. In the medical structure, with the development of information technology and the leap of intelligence, the application of uninterruptible power supply (UPS) system has become increasingly widespread and popular. In order to ensure patient safety, medical institutions need to ensure uninterrupted power supply in their buildings. Therefore, UPS uninterruptible power supply has become indispensable. Compared to commercial or industrial use, medical institutions require higher standards for UPS uninterruptible power supply protection systems. Most of the electrical loads in hospitals are primary and secondary loads, which require high continuity and reliability of power supply. Air conditioning system equipment is the main power consuming equipment in hospitals and requires focused management of electricity usage; Class II medical facilities have high requirements for power supply continuity and reliability, and require comprehensive monitoring; Important medical technology laboratory equipment is sensitive to power quality and requires special attention.
The UPS equipment room should be equipped with fire extinguishers and comply with the relevant provisions of the “Code for Design of Fire Extinguisher Configuration in Buildings” GB50140.